Thank you for choosing to fulfill your operational requirements for the Circuit Breaker NSN parts you require with Buy Ground Support Equipment. On this page, you can submit a quote request for Sensata Technologies Inc part number APL11-1-53F-403, a component that can also be found by inputting NSN 5925-01-458-0355 in our search engine. Alongside part number APL11-1-53F-403, we also have a wide range of other related items available, all of which can be traced back to a wealth of trusted manufacturers on our Approved Vendor List (AVL).
Buy Ground Support Equipment works with numerous government and defense agencies, so we use CAGE Codes like 81541 to uniquely identify items and their manufacturers in a standardized manner. We also utilize Federal Supply Classes (FSCs) to organize our inventory, ensuring customers can find Sensata Technologies Inc part number APL11-1-53F-403 by the FSC designation 5925 Circuit Breakers with ease. That being said, we encourage you to complete the RFQ form below for NSN 5925014580355 or any others that you are interested in, and we will provide you with a customized sourcing solution in 15 minutes or less. For one-on-one assistance, contact us via phone or email at any time; we are available 24/7x365!
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-458-0355 Item PartTypeName: CIRCUIT BREAKER | 5925 | 014580355 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
A | 0 | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
APL11-1-53F-403 | 5 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 2.490 INCHES NOMINAL |
ADAT | BODY WIDTH | 1.500 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.667 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.060 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.150 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.850 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 2 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 65.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 16.500 MINIMUM AT 200 PCT ALL LOCATIONS AND 70.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 4 THREADED STUD |
If You’re Ever Looking for NSN parts Or Have an Aircraft On Ground Situation, Don’t forget That We offer Competitive Pricing and Guaranteed On-Time Delivery.